What does it mean if I get an offline alarm?

What does it mean if I get an offline alarm?

An offline alarm refers to a network connectivity issue at the network gateway interface. This alarm is alerting the user that the Blue Pillar Aurora application cannot communicate with the network gateway interface. This not related to a particular piece of equipment, but rather the gateway the equipment is connected to. The Blue Pillar Gateway Reference Guide is useful literature in troubleshooting this alarm.

  • The gateway should be visually inspected for power and to ensure the network cable is plugged in.
  • Powering down and repowering the gateway may correct some issues. The process described in detail in the Blue Pillar Gateway Reference Guide
  • If the network cable is plugged in, network activity should evident as described in the Blue Pillar Gateway Reference Guide.
  • If network activity is not observed, the network cable should be inspected to ensure it is correctly installed in the data closet and connected to the correct port.
  • If the Blue Pillar Gateway is showing network activity but the alarm is still present, the facility IT team should be contacted and asked to check the switch and port. They will normally ask for the device IP and MAC address. This information can be found on the gateway device itself or on the Blue Pillar drawings for your facility. If unable to locate this information, please contact Blue Pillar Customer Support.
    • Related Articles

    • What does it mean if I get a comm alarm?

      A comm alarm is equipment specific meaning that it affects only the equipment that it refers to. This alarm is alerting the user that the network gateway interface is not receiving Modbus communication from the affected equipment. This can happen for ...
    • Aurora Application Programming Interface (API)

      API Filter The API exists as an endpoint on the Aurora Server and allows for the retrieval of live and historical data by filter or individual tag.  A filter can be created in Aurora by grouping a set of tags together for retrieval through the API. ...
    • Alarm: Generator Not Communicating With Meter

      Troubleshooting Steps: Open the Aurora instance for the site that is experiencing this alarm. Navigate to the Operations tab and select Event History. In the upper left-hand side of the window, select the system that includes the entity producing the ...
    • How to run an Alarm History Report

      Alarm History Report Historical Alarm information is available in the Alarm History report.  It can provide Active and Inactive Alarms and Acknowledged Alarm Dates and Cleared Alarm Dates How to generate an alarm history report: Select the  reporting ...
    • How to access Emergency Power Management System (EPMS)

      EPMS The Emergency Power Management System (EPMS) screen is for monitoring and controlling equipment by system and for executing Load and No Load tests. How to access the EPMS: Select the Operations menu option. Select EPMS from the menu list and the ...