How to run multiple system tests

How to run multiple system tests

How to run multiple system tests:

  1. While on the EPMS screen and viewing a system, select the Start Event(s) button in the upper right-hand corner and the platform displays the Event Setup Wizard.

EPMS – Start Event


  1. Select the Test Type of Load in the description.

Event Setup Wizard        


  1. Select the Next button and the platform displays the event configuration screen.
  2. Use the default Report Title or change the name of the event.
  3. Use the default email or change/add an email separated by commas to receive the event reports.
  4. If applicable check the System Checklist items.
  5. Select an ATS Event Group.
  6. Use the default (suggested) Initiating ATS or select a different one.
  7. SKIP for Auto Load Test - Select “Initiate commands through the User Interface” only if each piece of equipment will be controlled manually from the platform User Interface.
  8. SKIP to use the default configured entries for “Block Time (sec)” and “Block Size”.
  9. SKIP to use the default configured “Time to wait to begin event data capture (min)”.
  10. Select the “Enforce 30% load rule to start test” for the system to start the test once the generator reaches 30% of the rated kW.
  11. Select the Next button to continue with the Event Setup Wizard to set up the next system for the same test.

Event Setup Wizard      


  1. Repeat steps 4-12 to set up the next system in the test.
  2. Select the Next button to continue with the Event Setup Wizard to setup.
  3. Expand the details of the systems by clicking on the (+) symbol next to each system name and the platform displays the event setup details.

Event Setup Wizard 


  1. Review your selections.
  2. Use the Previous button to make configuration changes.
  3. Use the Cancel button to cancel the event setup.
  4. When ready select the Finish Setup button and the platform will display a final confirmation screen.

Event Setup Wizard


  1. Select the Run Test button and the platform will start the test.

Event Setup Wizard


Warning:  the test will start after the Run Test button is selected!

EPMS – Systems Expanded


EPMS – Systems Collapsed 


  1. Monitor the test from the EPMS screen.
  2. To view each system’s test activity then click on the Collapse All link and then click on the system header to expand just that system for full viewing.
  3. The platform will conduct system tests simultaneously.
  4. The platform will initiate the test and send commands to the ATS(s) to transfer to emergency power.
  5. The platform sets the event status to Test and the equipment status displays the number of active equipment.
  6. The ATS(s) will transfer and the generator(s) will start.
  7. In the equipment details, the platform displays the equipment in the test with an Active equipment status.
  8. Once all the ATS(s) have transferred then the platform will pause and wait a configured period before starting the event timer.
  9. When the event time remaining reaches 00:00:00 then the platform will send stop commands to the ATS(s) to re-transfer to normal power.
  10. The ATS(s) will re-transfer and the generator(s) will stop.
  11. Once all the ATS(s) have re-transferred and the generator(s) cooldown has completed then the platform will end the event.

Note:  the event can be canceled at any time by clicking on the Cancel Event button.


    • Related Articles

    • How to run a Manual Load Test

      EPMS How to run a Manual Load Test: While on the EPMS screen and viewing a system, select the Start Event button and the platform displays the Event Setup Wizard. EPMS – Start Event Select the Test Type of Manual in the description. Event Setup ...
    • How to run an Auto Load Test

      EMPS How to run an Auto Load Test: While on the EPMS screen and viewing a system, select the Start Event button and the platform displays the Event Setup Wizard. EPMS – Start Event Select the Test Type of Load in the description. Event Setup Wizard  ...
    • How to run an Auto No Load Test

      EPMS How to run an Auto No Load Test: While on the EPMS screen and viewing a system, select the Start Event button and the platform displays the Event Setup Wizard. EPMS – Start Event Select the Test Type of No Load in the description. Event Setup ...
    • How to run a Manual Load Test with User Interface Commands

      EMPS How to run a Manual Load Test with initiating commands from the user interface: While on the EPMS screen and viewing a system, select the Start Event button and the platform displays the Event Setup Wizard. EPMS - Start Event Select the Test ...
    • How to run a test when initiating commands from the equipment

      How to run a test when initiating commands from the equipment: While on the EPMS screen and viewing a system, select the Start Event button and the platform displays the Event Setup Wizard EPMS – Start Event Select the Test Type of Manual Config in ...