Aurora Classic Release Notes v5.11

Aurora On-prem Release Notes v5.11

Aurora On-prem

Alarm History Report

The Alarm History Report was updated to sort the alarm active data time in descending order.


Aurora Runtime

In the Aurora Runtime we removed error logging for Building_Energy, KPIs and Site_Energy tags missing an entity status since these tags do not have a status.

Defect Fixes

Functional Area

Description of Defect

Trending

The 2nd end date for trending period over period was getting set when the screen was opened and when a new date was selected it was not honored.  As a result, the scale on the trending graph was incorrect. 

Trending

Trending data was getting blended when there are multiple devices associated to an entity and some of the devices have the same tag name.  This has been corrected by displaying the data element by its tagname_entityname_devicename. 

Trending

When trending a duration less than 15 minutes the application was not defaulting to the minute data interval and the seconds data interval was not an option.

API

API communication stopped gathering data.  

Live View

Meters in an alarm state not connected to a bus bar in the live view were missing the alarm indicator.

Live View

Each time the Live View zoom in/out was selected the application would do an additional zoom in or out by 5% on its own.  Which looked like the screen was flickering.

Live View

Pan/Centering was occurring each time the Live View was moved by the User.  Changed the Pan/Centering to only occur when the Live View is opened for the first time during each session.

Alarms

Alarm email notifications were delayed when the service had a lot of data to process.

Demand Response Alarm

Demand Response Stop Command Alarms were staying active even though the command was successfully processed.

Operational Report

When an ATS did not have the Time to Available tag then the ATSs were not being displayed on the report.

EPMS System Error

When the emergency power supply system has a generator with a ENGINE_NOT_IN_AUTO tag as null and the Control Manager detects the test bit as high, then the application displays an ERROR on the EPMS page (rotating with TEST status).  The test completes normally. 

Login/Default Home Page

After logging into the application displayed a blank screen when the configured default home page should have rendered.

Runtime Formulas

Runtime Formulas that Cross Multiple Devices were Not Updating with Correct Device Reference.

Installer

Updated the Installer to drop/remove tables and stored procedures that no longer are needed.

Project Frog Integration

Project Frog External Integration was missing data for mapped tags for a period.  The Integration Request Data has been changed to use Hawaii Standard Time to fix the issue.

Alarm History Stored Procedure

The Alarm History stored procedure was not filtering out inactive tags.  As a result, a 500 error was produced in the API Log.



    • Related Articles

    • Aurora On-prem Release Notes v5.12

      Aurora On-prem Supported Web Browser Notification Upon accessing the Aurora Platform the application will check the internet browser being used and will display a warning message if the browser used is unsupported.  The official supported web browser ...
    • Aurora Application Programming Interface (API)

      API Filter The API exists as an endpoint on the Aurora Server and allows for the retrieval of live and historical data by filter or individual tag.  A filter can be created in Aurora by grouping a set of tags together for retrieval through the API. ...
    • Aurora On-prem Release Notes v6.1

      Aurora On-Prem Web Browser Since the retirement of IE 11 our new supported web browser is Google Chrome.   Generator Monitoring via Camera       The embedded frame for the web camera in the EPMS screen and the Generator details has been replaced with ...
    • Aurora On-prem User Guide v6.1

      To view the Aurora On-prem User Guide select the download option below.
    • How to run an Alarm History Report