Alarm: Generator Not Communicating With Meter

Alarm: Generator Not Communicating With Meter

Troubleshooting Steps:

  1. Open the Aurora instance for the site that is experiencing this alarm.
  2. Navigate to the Operations tab and select Event History.
  3. In the upper left-hand side of the window, select the system that includes the entity producing the alarm.
  4. Then re-cycle the selection by clicking on the Refresh button.
  5. Locate the last event where the generator was running.
  6. Perform trends on the Engine_Running and Meter_Comm_Alarm tags during this event. This alarm should only be active if the Horner is not communicating with the meter during an engine run event. The Horner will attempt to re-initialize communications, but if this fails, the alarm will return to a "true" state.

Alarm Configuration:


Resolution:

This failure can be caused by blown fuses, incorrect wiring layout, or breaks in the wiring. The meter may have failed as well. A technician will need to be dispatched in order to validate and repair these findings.

Normal Status:


Meter Communication Issue:


 


    • Related Articles

    • How to run an Alarm History Report

      Alarm History Report Historical Alarm information is available in the Alarm History report.  It can provide Active and Inactive Alarms and Acknowledged Alarm Dates and Cleared Alarm Dates How to generate an alarm history report: Select the  reporting ...
    • What does it mean if I get a comm alarm?

      A comm alarm is equipment specific meaning that it affects only the equipment that it refers to. This alarm is alerting the user that the network gateway interface is not receiving Modbus communication from the affected equipment. This can happen for ...
    • Aurora On-prem Release Notes v5.11

      Aurora On-prem Alarm History Report The Alarm History Report was updated to sort the alarm active data time in descending order. Aurora Runtime In the Aurora Runtime we removed error logging for Building_Energy, KPIs and Site_Energy tags missing an ...
    • How to run a Report

      Reports Aurora Platform provides a group of reports that provide up to date operational information. Note:  See Event History in this User Guide for Compliance Reports. How to generate a report: Select the  reporting icon in the platform header and ...
    • How to view Event History and Details

      Event History The Event History provides all the events that occur for each emergency power supply system by date in a calendar view.  The calendar view has been updated to filter by event type, event status and compliance status for systems ...