How to run an Auto Load Test with 30% Load Required:
- While on the EPMS screen and viewing a system, select the Start Event button and the platform displays the Event Setup Wizard.
- Select the Test Type of Load in the description.
- Select the Next button and the platform displays the event configuration screen.
- Use the default Report Title or change the name of the event.
- Use the default email or change/add an email separated by commas to receive the event reports.
- If applicable check the System Checklist items.
- Select an ATS Event Group.
- Use the default (suggested) Initiating ATS or select a different one.
- SKIP for Auto Load Test - Select “Initiate commands through the User Interface” only if each piece of equipment will be controlled manually from the platform User Interface.
- SKIP to use the default configured entries for “Block Time (sec)” and “Block Size”.
- SKIP to use the default configured “Time to wait to begin event data capture (min)”.
- Select the “Enforce 30% load rule to start test” for the system to start the test once the generator reaches 30% of the rated kW.
- Select the Next button to continue with the Event Setup Wizard.
- Expand the system details by clicking on the (+) symbol next to the system name and the platform displays the event setup details.
- Review your selections.
- Use the Previous button to make configuration changes.
- Use the Cancel button to cancel the event setup.
- Select the Finish Setup button and the platform will display a final confirmation screen.
- Select the Run Test button and the platform will start the test.
Warning: the test will start after the Run Test button is selected!